Trane · Air conditioner

HL Hard lock: low pressure (LPCO)

Critical severity Trane 5TTR7

What the control is telling you

Low suction pressure reached hard-lock level (fault column says soft-lock). Manual lists only the meaning (A1000BA board); steps are general checks drawn from other sections of the guide.

Applies to: Trane 5TTR7 multi-speed AC (5TTR7024A-060A)

Likely causes

  • Low charge / leak
  • Service valve not fully open
  • Low indoor airflow or iced coil
  • Restriction

Test and repair steps

  1. Check charge (low charge trips LPCO).
  2. Confirm both service valves are fully open.
  3. Check indoor airflow, filter and indoor coil in cooling; outdoor coil icing in heating.
  4. Check for restrictions in liquid line or drier.

Settings for these units

Outdoor unit placement · Trane 5TTR7

ItemValue
Above unit5 ft clear
Service side3 ft
Walls / shrubs12 in. min
Pad1 in. larger than unit all round, level, separate from house
Cold climate (HP)raise 3-12 in. above pad
Within 1 mile of salt wateradd BAYSEAC001 if no factory salt shield
Operating rangecooling 55-120 F, heating 0-66 F

Avoid bedroom walls and under roof drip lines.

Dimensions and weights · Trane 5TTR7

ModelH x D x W (in.)Weight (lb)
5TWR7024A41 x 30 x 33181
5TWR7036A41 x 30 x 33194
5TWR7048A41 x 34 x 37231
5TWR7060A41 x 34 x 37241
5TTR7024A41 x 30 x 33176
5TTR7036A41 x 30 x 33189
5TTR7048A41 x 34 x 37226
5TTR7060A41 x 34 x 37236

Weights are estimated, uncrated.

Models that show this code

4 models in Trane 5TTR7

5TTR7024A5TTR7036A5TTR7048A5TTR7060A

Other codes on the same units

  • Fd Discharge temperature sensor fault
  • HC Hard lock: compressor over-current
  • HF Hard lock: outdoor fan over-current
  • HH Hard lock: high pressure (HPCO / DTC)
  • Hd Hard lock: high discharge temperature
  • LC Lockout: compressor over-current
  • LF Lockout: outdoor fan over-current
  • LH Lockout: high pressure (HPCO / DTC)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane ODR-SVN002E-EN (5TTR7/5TWR7 installer's guide) - section Integrated Variable Speed Control Board LED Indicators, Table 18 (A1000BA models). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.