Rinnai · Tankless water heater

10 Air supply or exhaust blocked / condensate trap full

Critical severity Non-SENSEIRH180 hybridSENSEI RX/CXSENSEI

What the control is telling you

The unit detects restricted combustion air intake or exhaust. On SENSEI and SENSEI RX/CX units, it also triggers when a blocked condensate drain backs up into the internal trap.

Applies to: SENSEI, SENSEI RX/CX and non-SENSEI tankless (condensate trap check: SENSEI and SENSEI RX/CX only)

Likely causes

  • Clogged or frozen condensate drain line backing up the internal trap (SENSEI, SENSEI RX/CX)
  • Dirty inlet air filter
  • Vent installed wrong: unapproved materials, poorly seated or unsealed joints, too long, bad clearances
  • Vent pipe crushed by foam sealant, or debris/water/insects inside the vent
  • Fan wheel, housing, air duct or check valve restricted or stuck
  • Debris in the burner, or blocked heat exchanger fins
  • Incorrect altitude parameter, manifold gas pressures or DIP switch settings
  • Faulty fan motor/bearing, fan wiring harness or PC Board

Test and repair steps

  1. SENSEI/RX/CX Make sure the condensate line drains. A blocked or frozen line backs up into the internal trap and triggers code 10. Then clean the inlet air filter (top right, under the front cover).
  2. All Inspect the whole intake and exhaust system inside and out: clearances, approved vent materials for this model, and joints fully seated and sealed.
  3. Warning: Never leave the heater running with intake or exhaust disconnected. The next step is a test only. Reconnect the vent right away.
  4. All (only if it codes out while you are there): Disconnect the exhaust from the top of the unit and run hot water. If it runs without the code, the restriction is in the vent system.
  5. If it still codes out mark each vent joint, take the vent apart and check insertion depth. Reassemble with the vent supplier's lubricant. Bad joints can leak exhaust and cause code 10.
  6. Confirm equivalent vent length is within limits (concentric: 90° elbow = 6 ft, 45° = 3 ft). Non-SENSEI: also set the vent-length DIP switches to match.
  7. Make sure foam sealant at the wall penetration has not crushed the pipe (check with a flashlight or camera). Open joints and look for water, condensation, insects or debris.
  8. Confirm termination clearances to other vent terminals and to overhangs, grade, walls, porches and obstructions, per the venting instructions.
  9. Caution: Turn off power. Remove the fan and check the wheel, housing and air duct for restrictions. SENSEI: also make sure the check valve behind the fan is not stuck. Refit the fan and test.
  10. SENSEI/RX/CX Confirm the high altitude parameter. Non-SENSEI (gas-qualified only): confirm low/high fire manifold pressures and altitude DIP switches. A wrong setting can trigger code 10 via the burner sensor.
  11. Non-SENSEI – WARNING (VE, VA, VB, VC, KA, RH-180, KCM): Turn off power, gas and water. Clear the manifold orifices and burner chamber, then blow out fins at 120 psi (wear glasses/mask) or replace the heat exchanger.
  12. SENSEI/RX/CX – WARNING: Turn off power, gas and water before removing the heat exchanger assembly.
  13. SENSEI/RX/CX Separate the burner, clean debris from the burner and air chamber, and check the back of the burner. Do NOT blow out the burner with compressed air. Blow out heat exchanger fins at 120 psi or replace.
  14. Warning: Disconnect power and gas before replacing parts. Other possible causes: faulty fan motor or bearing, fan wiring harness, PC Board, or wrong DIP switch settings (non-SENSEI).

Settings for these units

RSC supply connection sizes · SENSEI

ConnectionSize
Gas3/4 in. NPT
Cold inlet3/4 in. NPT
Hot outlet3/4 in. NPT
Condensate drain1/2 in. NPT
Pressure relief valveM33 thread

The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.

Condensate drain line must stay at least 1/2 in. over its whole length.

RSC water quality limits · SENSEI

ContaminantMaximum level
Total hardnessUp to 200 mg/L
AluminumUp to 0.2 mg/L
ChloridesUp to 250 mg/L
CopperUp to 1.0 mg/L
Dissolved CO2Up to 15.0 mg/L
IronUp to 0.3 mg/L
ManganeseUp to 0.05 mg/L
pH6.5 to 8.5
TDSUp to 500 mg/L
ZincUp to 5 mg/L

Damage from water above these limits is not covered by warranty.

Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.

Models that show this code

89 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI

C199eC199iCU160eCU160iCU199eCU199iCX160iCX199iCXP160iCXP199iR50LSiR63LSe2R75LSeR75LSiR94LSeR94LSiR98LSeR98LSe-ASMER98LSiR98LSi-ASMERC80eRC80iRC98eRC98iRE140eRE140iRE160eRE160iRE180eRE180iRE199eRE199iREP160eREP160iREP199eREP199iRH180RL75eRL75e(A)RL75iRL75i(A)RL94eRL94iRLX94iRSC160eRSC160iRSC199eRSC199iRU130eRU130iRU160eRU160iRU180eRU180iRU199eRU199iRU80eRU80iRU90eRU98e

Other codes on the same units

  • 02 Burner did not operate during freeze protection
  • 03 Power interrupted during bath fill
  • 05 Bypass flow control device fault
  • 07 Circulation flow rate below 2.1 GPM
  • 11 No ignition
  • 12 Flame failure
  • 13 Combustion fault
  • 14 Thermal fuse or overheat sensor tripped

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.12–15. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.