Noritz · Tankless water heater
91 Gas conversion not done correctly
What the control is telling you
EZ/NRCR: the unit's gas conversion was not completed correctly.
Applies to: Noritz EZ111/EZ98/EZ71 and NRCR111/NRCR92
Likely causes
- LP orifice installed but gas type not changed in the app/display (or the reverse)
- Gas conversion connector missing (NG to LP)
- Wrong conversion kit
Test and repair steps
- Warning: Do not run the unit on LP until conversion is complete and verified; exhaust odor or burning eyes can mean a bad conversion.
- Confirm the kit CK-85 = NG to LP (includes the gas conversion connector), CK-84 = LP to NG.
- Check the orifice, o-rings and emission port cap gasket were replaced.
- Plug in the LP conversion connector and set the gas type in the EZ Start Plus app (Unit Setting > Convert Gas Type) or the display.
- Check inlet gas pressure and offset pressure at the gas valve with a digital manometer, and check combustion with a gas analyzer.
- Leak test, then fill out and attach the gas conversion sticker.
Settings for these units
Indoor clearances (required and recommended) · Noritz NRCR
| Location | Required | Recommended (service) |
|---|---|---|
| Top | 12 in. (300 mm) | 3 in. (76 mm) above and below exhaust |
| Front | 4 in. (100 mm) | 24 in. (610 mm) |
| Sides | 3 in. (76 mm) | 8 in. (203 mm) |
Required clearances apply to both combustible and non-combustible materials.
Recommended space is for service and quick access to gas and water shut-offs.
Operation panel menu settings and defaults · Noritz EZ, Noritz NRCR
| Setting | Options | Default |
|---|---|---|
| Max Set Temperature (power off) | 100-140 F in 5 F steps; 37-48 C, 50-60 C | 120 F / 50 C |
| Recirc ON/OFF | ON / OFF | OFF |
| Recirc Mode | Always OFF, Always ON, Manual Timer, Auto Learning (NRCR) | Always OFF |
| Vacation Mode | Active / Inactive | Inactive |
| Flow Meter Alarm | 10-60 gal (5 gal steps), 70-100 gal (10 gal steps), OFF | Alarm OFF |
| Drain Water (power off) | Start / Cancel | Cancel |
| Scale Flushing (power off) | Start / Cancel | Cancel |
| Audible Alarm | ON / OFF | ON |
| Screen Lock | Active / Inactive (4-digit password) | Inactive |
| Units (first 10 min after power-up, power off) | [F/gal/ft] or [C/L/m] | [F/gal/ft] |
| Power Saving Dis. / Backlight | ON-OFF / Power Save ON-OFF | ON / Power Save ON |
| Brightness / Contrast / Touch Sound | Bright-Normal-Dim-Dark / -15 to +15 / ON-OFF | Normal / Standard / ON |
Setting 125 F (55 C) or higher needs Max Set Temperature raised first; the panel warns about scald risk.
Default Settings resets everything in Settings except Screen Lock (hold OK about 5 s).
- Water quality limits · Noritz EZ, Noritz NRCR
Models that show this code
5 models in Noritz EZ, Noritz NRCR
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Noritz EZ/NRCR Owner's Guide (Rev. 10-25), Checking for error conditions / Gas conversion, p.31, 33; Noritz NRCR Pro training (NRCR92/NRCR111, Printable V3), Field gas conversion, p.3-6. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.