Navien · Tankless water heater

E109 Fan motor abnormal

High severity Navien NPE-2

What the control is telling you

The combustion fan is not reaching or holding the commanded speed.

Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2

Likely causes

  • Dirty air intake filter
  • Fan motor or wiring fault
  • Vent restriction

Test and repair steps

  1. Clean the air intake filter (manual's listed action).
  2. Run Service menu > 3. Test Mode > 1. Fan Motor: the fan ramps from 0 to max and back; check for noise or sticking.
  3. Check Status Information > 13. Current RPM while firing.
  4. Check the fan connector and wiring.
  5. Reset once with the Back button on the front panel and note whether the code returns.
  6. Code back after a reset? Stay at the unit and phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Installation clearances (indoor / outdoor) · Navien NPE-2

SideIndoorOutdoor
Top9 in. (229 mm)36 in. (900 mm)
Back0.5 in. (13 mm)0.5 in. (13 mm)
Front4 in. (100 mm)24 in. (600 mm)
Sides3 in. (76 mm)3 in. (76 mm)
Bottom12 in. (300 mm)12 in. (300 mm)

Vent clearance to combustibles is 0 in.

Outdoor: use the Navien Outdoor Vent Kit; keep 3 ft from an eave to the top of the vent terminals; mild climates only.

Water quality limits and flushing schedule · Navien NPE-2

Hardnessgrains/gal (mg/L)TreatmentFlush frequency
Soft0-4 (0-60)NoneNone
Moderately hard4-7 (61-120)None requiredOnce a year
Hard7-9 (121-160)Softener or Navien PeakFlow recommendedOnce a year
Very hard9-12 (161-200)Softener or PeakFlow highly recommendedResidential once a year; commercial twice a year
Extremely hard>12 (200)Softener or PeakFlow required-

Other max levels: hardness 200 mg/L, chloride 250, copper 1.0, iron 0.3, manganese 0.05, sulfate 250, TDS 500, zinc 5, chlorine 4 mg/L; aluminum 0.05-0.2 mg/L; pH 6.5-8.5.

Flushing is advised when no treatment device is installed; use white vinegar or a tankless descaler.

Models that show this code

7 models in Navien NPE-2

NPE-150S2NPE-180A2NPE-180S2NPE-210A2NPE-210S2NPE-240A2NPE-240S2

Other codes on the same units

  • E031 Burner overheating
  • E046 Limit control abnormal
  • E047 Exhaust thermistor open or shorted
  • E060 Dual venturi abnormal
  • E110 Abnormal air pressure
  • E407 Hot water outlet thermistor open or shorted
  • E421 Cold water inlet 1 thermistor open or shorted
  • E432 Cold water inlet 2 thermistor open or shorted

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.17. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.