Navien · Boiler

E762 Vent pipe not fully inserted (VID)

Critical severity Navien NHB-HNavien NFB-H

What the control is telling you

The Vent Installation Detector does not sense the exhaust pipe fully inserted in the collar. NHB-H manual: insert 2-3/4 in (70 mm). NFB-H error table says 3 in, but its venting section says 2-3/4 in (70 mm).

Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers

Likely causes

  • Exhaust pipe not pushed fully into the collar
  • Wrong size pipe (VID needs a correctly sized 2.0 in pipe) or deformed/damaged pipe
  • Pipe misaligned or moved vertically
  • Common vent collar kit fitted without the VID jumper wire

Test and repair steps

  1. Warning: A pipe that is not fully seated can leak carbon monoxide. Do not run the boiler until it is fixed.
  2. Cut the pipe square, deburr, mark 2-3/4 in (70 mm) from the end, wet with water (not grease) and twist it in until it bottoms and the mark is hidden.
  3. Put a straight piece on the collar. Do not fit a street elbow right at the collar.
  4. Tighten the collar clamp with an 8 mm socket.
  5. Replace a damaged or out-of-round vent pipe.
  6. With a Navien common vent collar kit, connect the supplied VID jumper wire to the wire labelled VID.
  7. Bubble-test all vent joints with the boiler running. The VID does not detect leaks or separated joints further along the vent.

Settings for these units

Installation clearances (indoor) · Navien NHB-H

SideMinimum clearance
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)
Vent to combustibles0 in

Bracket gives 5/8 in (16 mm) from the wall; studs at 16 in on centre.

Common vent installs: 36 in above the top and 24 in in front are recommended for service.

Installation clearances (indoor) · Navien NFB-H

SideMinimum clearance
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)
Vent to combustibles0 in

Do not install on carpet; indoors only.

Remove the wood pallet and refit the 6 screws to keep the cabinet airtight.

Models that show this code

6 models in Navien NHB-H, Navien NFB-H

NFB-175HNFB-200HNHB-055HNHB-080HNHB-110HNHB-150H

Other codes on the same units

  • E594 EEPROM fault
  • E615 Memory fault
  • E736 Cascade communication fault
  • E740 Outdoor sensor not detected
  • E777 Low water cutoff activated
  • E782 Front panel communication fault
  • E784 Zone controller communication fault
  • E786 Improper front panel detected

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.