Lennox · Heat pump
Green SLOW flash / Red OFF High pressure fault
What the control is telling you
The high pressure switch (S4) opened (trips at 590 +/- 15 psig, auto reset) and the control stopped the compressor and counted one strike.
Applies to: Lennox EL16KP1 (Elite) and ML14KP1 (Merit) R-454B heat pumps, sizes -018 to -060, demand defrost control A108 (CMC1)
Likely causes
- Restricted airflow over the indoor or outdoor coil (dirty coil, filter, blocked fan)
- Wrong refrigerant charge
- Wrong metering device installed or expansion valve not working properly
- Pressure switch or sensor mounted wrong or loose connection
Test and repair steps
- Clean the outdoor coil and make sure the outdoor fan runs at the right speed and current.
- In heating, check indoor airflow (dirty filter, closed registers, blower speed) - the indoor coil is the condenser.
- Check the charge with the subcooling method; an overcharge raises head pressure.
- Compare operating pressures with the Normal Operating Pressures table for the unit size.
- Confirm the correct indoor expansion valve is installed and working.
- Check the high pressure switch (S4, opens at 590 +/- 15 psig) wiring at HS-PS; make sure pressure switches and sensors are tight on the system.
Settings for these units
Outdoor unit clearances · Lennox EL16KP1
| Location | Clearance |
|---|---|
| Service side (one side next to control box) | 30 in. (762 mm) |
| One of the other three sides | 36 in. (914 mm) |
| One of the remaining two sides | 12 in. (305 mm) |
| Last side | 6 in. (152 mm) |
| Between two units | 24 in. (610 mm) |
| Top | 48 in. (1219 mm) |
| Above roof surface (roof mount) | 6 in. (152 mm) minimum |
Increase clearances where snow/ice can fall on the unit or air can recirculate (decks, tight spaces).
Wind barrier, if used, 24 in. (610 mm) from the unit.
Outdoor unit clearances · Lennox ML14KP1
| Location | Clearance |
|---|---|
| Service side (one side next to control box) | 24 in. (610 mm) |
| One of the other three sides | 36 in. (914 mm) |
| One of the remaining two sides | 12 in. (305 mm) |
| Last side | 6 in. (152 mm) |
| Top | 48 in. (1219 mm) |
| Multi-unit, between units | 12 in. (305 mm) minimum [18 in. (457 mm) recommended] or 24 in. (610 mm) depending on layout |
| Multi-unit service side | 24 in. (610 mm) recommended |
| Above roof surface (roof mount) | 6 in. (152 mm) minimum |
Multi-unit spacing (A/B) depends on single row, wall or multiple rows layout - see figure on p.7.
Increase clearances where snow/ice can fall on the unit or air can recirculate.
Models that show this code
14 models in Lennox EL16KP1, Lennox ML14KP1
Other codes on the same units
- Green FAST flash / Red ON Discharge line temperature lockout
- Green OFF / Red FAST flash Discharge sensor fault
- Green OFF / Red OFF No power to the demand defrost control
- Green OFF / Red ON Low pressure lockout
- Green OFF / Red SLOW flash Low pressure fault
- Green ON / Red OFF High pressure lockout
- Green ON / Red ON Demand defrost control failure
- Green SLOW flash / Red ON Discharge line temperature fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL16KP1 Unit Information 100195 / ML14KP1 Unit Information 100108, Table 4 Demand Defrost Control (A108) Diagnostic LEDs, p.32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.