Lennox · Furnace

E112 Ground not detected

High severity EL296UHVLennox SL280UHVLennox ML180UHELennox SL297NV

What the control is telling you

The control cannot detect an earth ground and shuts the system down.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Missing or broken equipment ground

Test and repair steps

  1. Warning: Disconnect power before working on wiring.
  2. Verify the ground conductor is connected at the furnace and back to the panel.
  3. Check ground at the control AC volts between line neutral and the C terminal should not exceed 2 VAC at idle, 5 VAC with inducer/ignitor on, 10 VAC with blower on; a wide swing under load means a poor ground. Line hot to neutral should be 97-132 VAC.
  4. Repair or install a proper earth ground.
  5. Restore power; system resumes 5 seconds after the fault clears.

Settings for these units

Recommended filter size by cabinet width · EL296UHV

Cabinet widthSide returnBottom return
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is the quantity of filters.

Filters are field supplied and installed outside the furnace; inspect monthly.

Recommended filter size by cabinet width · Lennox SL280UHV

Cabinet widthSide returnBottom return
14-1/2 in.16 x 25 x 1 in. (1)14 x 25 x 1 in. (1)
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is filter quantity; filters are field supplied.

Never run the unit without a filter installed.

Models that show this code

34 models in EL296UHV, Lennox SL280UHV, Lennox ML180UHE, Lennox SL297NV

EL296UH045XV36BEL296UH070XV36BEL296UH090XV36CEL296UH090XV48CEL296UH090XV60CEL296UH110XV48CEL296UH110XV60CEL296UH135XV60DML180UH045E36AKML180UH045XE36AKML180UH070E36AKML180UH070E36BKML180UH070XE36AKML180UH070XE36BKML180UH090E48BKML180UH090E60CKML180UH090XE48BKML180UH110E60CKML180UH110XE60CKML180UH135E60DKSL280UH060NV36ASL280UH070V36ASL280UH080NV48BSL280UH080NV60CSL280UH090V36BSL280UH090V48BSL280UH090V60CSL280UH100NV60CSL280UH110V60CSL280UH135V60DSL297UH040NV36BSL297UH060NV36BSL297UH080NV48CSL297UH080NV60C

Other codes on the same units

  • E105 Device communication problem
  • E106 Twin communication fault
  • E110 Low line voltage
  • E111 Line voltage polarity reversed
  • E113 High line voltage
  • E114 Line frequency out of range
  • E115 Low 24 VAC
  • E116 High 24 VAC

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.33; Ignition Control 107045-XX Diagnostic Codes table, p.40, Proper Ground and Voltage p.85. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.