ICP · Heat pump

3 Short cycling

Medium severity ICP N4H3 Heat Pump

What the control is telling you

Compressor runs only briefly.

Applies to: ICP N4H3 R-410A split heat pump (manual 428 01 5103 02); Comfort Alert codes apply only to units factory-fitted with the Comfort Alert module

Likely causes

  • Intermittent thermostat demand
  • Time delay relay or control board defective
  • High pressure switch tripping (see Code 2)
  • Low pressure switch tripping (see Code 1)

Test and repair steps

  1. Check the thermostat and Y wire for loose connections.
  2. Check any time delay relay or control board.
  3. If a high pressure switch is fitted, follow Code 2 checks.
  4. If a low pressure switch is fitted, follow Code 1 checks.

Settings for these units

Outdoor unit clearances · ICP N4H3 Heat Pump

LocationMinimum
Above unit (discharge)48 in. (1.2 m)
Each coil side (intake)18 in. (457 mm)
One coil side, reduced (unit to structure)6 in. (152 mm)
Control box corner and service panel24 in. (610 mm)
Between side-by-side units18 in. (457 mm)
Roof overhang above unit (with gutters)48 in. (1.2 m) vertical

Small objects (post, fence end): clearance about equal to the object width.

Do not install under an overhang without gutters.

Models that show this code

1 model in ICP N4H3 Heat Pump

N4H3

Other codes on the same units

  • 1 Long run time
  • 2 System pressure trip
  • 4 Locked rotor
  • 5 Open circuit
  • 6 Open start circuit
  • 7 Open run circuit
  • 8 Welded contactor
  • 9 Low voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP N4H3 Installation Instructions 428 01 5103 02, Comfort Alert Diagnostics Codes (Figure 18), p.20. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.