Gree · Heat pump
H7 Compressor lost synchronism
What the control is telling you
The inverter lost track of the compressor rotor position.
Applies to: Gree Sapphire 9-24k (SAP..HP230V1A), Livo GEN4 30-36k (4LIV..HP230V1A), Vireo GEN3 9-24k (3VIR..HP115/230V1A), Multi21+ 18-24k multi-zone (MULTI..HP230V1CO)
Likely causes
- Compressor off less than 3 min (pressures not equalized)
- Compressor U/V/W wiring loose or wrong sequence
- Supply voltage abnormal
- Overcharge or high pressure
- Outdoor fan not running or poor airflow
- Compressor or board fault
Test and repair steps
- Let the compressor stay off at least 3 min before restart.
- Check compressor wire connections and phase order.
- Check supply voltage.
- Correct an overcharge and clean the coils.
- Check the outdoor fan, its plug and capacitor.
- Replace AP1, then the compressor, if the code persists.
Models that show this code
14 models in Gree Sapphire, Gree Livo GEN4, Gree Vireo GEN3, Gree Multi21+
Other codes on the same units
- F8 Compressor slowed - high current
- F9 Compressor slowed - high discharge temperature
- H0 Compressor slowed - high indoor coil temp in heating
- H1 Defrost or oil return (status)
- H3 Compressor overload protection
- H4 System abnormal (overload)
- H5 IPM (inverter module) protection
- H6 Indoor fan motor not running / no feedback
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Gree Sapphire 9-12k (SAP09-12HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Sapphire 18-24k (SAP18-24HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Livo GEN4 30-36k (4LIV30-36HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Vireo GEN3 9-24k (3VIR..HP115-230V1A) service GREE_VIREOGEN3_SERVICE_090921.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Multi21+ multi-zone 18-24k (MULTI18-24HP230V1CO) service.pdf - section 9.1 Malfunction status sheet / 9.2 Malfunction Checking and Elimination. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.