Gree · Heat pump

C0 Communication fault IDU/ODU/wired controller

High severity Gree GMV6 Mini VRF

What the control is telling you

Indoor units, outdoor unit or the wired controller are not communicating.

Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))

Likely causes

  • D1/D2 wiring open, loose or mixed with H1/H2 or G1/G2
  • No power at an indoor unit

Test and repair steps

  1. Inspect the D1/D2 bus; it must be run separately from the H1/H2 and G1/G2 terminals.
  2. Confirm 208/230 VAC at L1/L2 on every indoor and the outdoor unit.

Models that show this code

3 models in Gree GMV6 Mini VRF

GMV-V36WL/C-T(U)GMV-V48WL/C-T(U)GMV-V60WL/C-T(U)

Other codes on the same units

  • b1 Outdoor ambient sensor open or shorted (15K)
  • b2 Defrost (coil) sensor open or shorted (20K)
  • b4 Sub-cooler liquid outlet sensor open or shorted (20K)
  • b6 Accumulator inlet sensor open or shorted (20K)
  • C1 Main board to DC-DC controller communication fault
  • C2 Main board to compressor drive communication fault
  • C3 Main board to fan drive communication fault
  • C4 Missing indoor units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.