Goodman · Heat pump

Yellow 6 flashes Open start circuit / lockout (older ComfortNet board)

Critical severity Goodman/Amana ComfortNet ASZC/GSZC/DSZC

What the control is telling you

Yellow LED 6 flashes. Red OFF = open start circuit; red ON = lockout after the fault was seen 4 times. Same as 06 / L6 on newer boards.

Applies to: Earlier ComfortNet condensers/heat pumps with the PCBHR101-103 or PBBGR101-102 outdoor control (green, yellow and red status LEDs) - ASXC/DSXC/ASZC/DSZC revisions before the PCBHR104 change

Likely causes

  • Compressor start winding open
  • Failed run capacitor or capacitor wiring
  • Compressor not wired correctly to the control
  • Faulty compressor wiring

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Check the run capacitor and its wiring; replace if weak or open.
  3. Measure compressor winding resistance (C-S, C-R, R-S); an open start winding means compressor replacement.
  4. Check compressor wiring and connections at the control and terminals.
  5. Lockout (red ON) needs a 24 VAC power cycle to clear.

Models that show this code

24 models in Goodman/Amana ComfortNet ASZC/GSZC/DSZC

ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, diagnostic/status LED table (PCBHR101-103, PBBGR101-102) p.65-69. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.