H8 High line voltage

High severity Goodman/Amana ComfortNet ASZC/GSZC/DSZC

What the control is telling you

Line voltage measured above 255 VAC. Clears when voltage drops back below 255 VAC.

Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18

Likely causes

  • Supply voltage too high

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Measure line voltage at the unit.
  3. Confirm the unit is on the supply voltage shown on the rating plate.
  4. Have the utility correct a high supply voltage.

Models that show this code

24 models in Goodman/Amana ComfortNet ASZC/GSZC/DSZC

ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601

Other codes on the same units

  • d2 System mismatch - indoor unit cannot supply required airflow
  • d3 Configuration mismatch - shared data does not match hardware
  • d4 Shared data from the loader rejected
  • E5 Outdoor control low-voltage fuse open
  • L1 Lockout - low pressure switch tripped 3 times
  • L2 Lockout - high pressure switch tripped 3 times
  • L6 Lockout - open start circuit detected 4 times
  • L7 Lockout - open run circuit detected 4 times

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.