Goodman · Air handler
Eb7 Blower motor missing shared data / failed to start 40 times
What the control is telling you
The motor does not have enough information to run properly, or it failed to start 40 times in a row.
Applies to: ComfortBridge communicating air handlers AVPTC**14 (B* revision board) and MBVC1201/1601/2001 modular blowers
Likely causes
- Control fault or wrong/missing shared data
Test and repair steps
- Verify the control is loaded with the correct shared data; reload with the BTSDL01 if needed.
- If data is correct and the fault persists, check the control and motor.
- Check the blower wheel turns freely, since repeated failed starts point to a mechanical bind.
Models that show this code
21 models in Goodman/Amana ComfortBridge AVPTC/MBVC
Other codes on the same units
- Eb3 Blower limiting on power, temperature or speed
- Eb4 Blower motor lost rotor control or high current
- Eb5 Blower motor failed to start 10 times
- Eb6 Blower shut down for voltage or power module temperature
- Eb9 Airflow lower than demanded
- EC1 Communication error with the outdoor unit
- Ed0 No shared data on the network
- Ed1 Invalid shared data
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Air Handler Troubleshooting Matrix (B*) p.59-60. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.