Goodman · Air conditioner

Comfort Alert 2 Yellow ALERT 2 flashes - system pressure trip

High severity Goodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)

What the control is telling you

Discharge or suction pressure out of limits, or the compressor overloaded.

Applies to: Amana ASX13 (CA revision) and ASX14 (1CA, 1BA and 421DA revisions) condensers fitted with the 2-wire Comfort Alert module

Likely causes

  • High head pressure
  • Poor airflow over outdoor coil (dirty, blocked, damaged)
  • Outdoor fan not running
  • Large return duct leak
  • Low pressure switch opening (if fitted) - see code 1 causes

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Clean and clear the outdoor coil.
  3. Check outdoor fan motor, capacitor and wiring.
  4. Check for overcharge or non-condensables.
  5. Inspect the return duct for leaks pulling in hot air.
  6. If a low pressure switch is fitted, follow the long-run checks too.

Models that show this code

142 models in Goodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)

ANX130181ANX130241ANX130301ANX130361ANX130421ANX130481ANX130601ANX130611ANX140181ANX140191ANX140241ANX140251ANX140301ANX140361ANX140371ANX140421ANX140431ANX140481ANX140601ASX130181ASX130241ASX130301ASX130361ASX130421ASX130481ASX130601ASX130611ASX140181ASX140191ASX140241ASX140251ASX140301ASX140311ASX140361ASX140371ASX140421ASX140431ASX140481ASX140601ASX160181ASX160241ASX160301ASX160311ASX160361ASX160371ASX160421ASX160481ASX160601ASX160611ASX180**1ABASXH5***10DSX160241DSX160361GSX110903GSX110904GSX111203GSX111204GSX130181GSX130241GSX130301

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman RS6200006r103 R-410A ASX/GSX/DSX/ASZ/GSZ/DSZ service (text export) - Goodman_R_410A_ASX_GSX_DSX_A_C_and_ASZ_GSZ_DSZ_HP_covers_GSX_GSZ_lines_GSXH5_GSZH5_service.txt - section Diagnostics Table: 2-Wire Comfort Alert Module. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.