EE9 High-stage pressure switch did not close
What the control is telling you
On a two-stage furnace the high-stage pressure switch does not close when the inducer goes to high speed. The furnace keeps running on low stage only. Flowcharts call this code E9.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Pressure switch hose blocked, pinched or connected wrong
- Blocked flue or intake, or vent too long / too many elbows
- Blocked condensate drain
- Weak inducer on high speed
- Bad switch or loose wiring
Test and repair steps
- Inspect the high-stage pressure switch hose and repair or replace it.
- Check the flue and intake piping for blockage and for correct length, elbows and termination.
- Check the drain system and front cover pressure switch.
- With a manometer, compare the negative pressure at high inducer speed with the switch rating; enough vacuum but open switch = replace the switch.
- Check inducer voltage and amps; replace the inducer if it cannot pull enough vacuum.
- Tighten or correct the pressure switch wiring and retest a high-fire call.
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
- EE4 Flame sensed with no call for heat
- EE5 Open fuse (short in low voltage wiring)
- EE6 Low flame signal
- EE8 High-stage pressure switch closed at start of heating cycle
- EAF R-32 sensor communication lost - mitigation mode
- EAL R-32 refrigerant leak detected - mitigation mode
- EAS R-32 sensor fault - mitigation mode
- EAr A2L relay fault - mitigation mode
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; Error Code E1, E2, E8, E9 flowchart p.36. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.