Daikin · Furnace

EE9 High-stage pressure switch did not close

Medium severity Daikin DR96TN/DD96TN

What the control is telling you

On a two-stage furnace the high-stage pressure switch does not close when the inducer goes to high speed. The furnace keeps running on low stage only. Flowcharts call this code E9.

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Likely causes

  • Pressure switch hose blocked, pinched or connected wrong
  • Blocked flue or intake, or vent too long / too many elbows
  • Blocked condensate drain
  • Weak inducer on high speed
  • Bad switch or loose wiring

Test and repair steps

  1. Inspect the high-stage pressure switch hose and repair or replace it.
  2. Check the flue and intake piping for blockage and for correct length, elbows and termination.
  3. Check the drain system and front cover pressure switch.
  4. With a manometer, compare the negative pressure at high inducer speed with the switch rating; enough vacuum but open switch = replace the switch.
  5. Check inducer voltage and amps; replace the inducer if it cannot pull enough vacuum.
  6. Tighten or correct the pressure switch wiring and retest a high-fire call.

Settings for these units

Normal status displays (7-segment) · Daikin DR96TN/DD96TN

ModeDisplay
IdleIdL
Continuous fanFAn
Cooling, low stage1AC
Cooling, high stage2AC
Gas heat, low stagegH1
Gas heat, high stagegH2
Factory (OEM) test modeEOL

These are normal operating displays, not fault codes.

Models that show this code

13 models in Daikin DR96TN/DD96TN

DD96TN0403BNDD96TN0603BNDD96TN0803BNDD96TN1005CNDR96TN0303ANDR96TN0403ANDR96TN0603ANDR96TN0603BNDR96TN0803BNDR96TN0804CNDR96TN1004CNDR96TN1005CNDR96TN1205DN

Other codes on the same units

  • EE4 Flame sensed with no call for heat
  • EE5 Open fuse (short in low voltage wiring)
  • EE6 Low flame signal
  • EE8 High-stage pressure switch closed at start of heating cycle
  • EAF R-32 sensor communication lost - mitigation mode
  • EAL R-32 refrigerant leak detected - mitigation mode
  • EAS R-32 sensor fault - mitigation mode
  • EAr A2L relay fault - mitigation mode

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; Error Code E1, E2, E8, E9 flowchart p.36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.