Carrier · Heat pump

32 Low pressure trip

Medium severity Carrier Infinity 18VS 25VNA8Carrier 2-stage 24ANB/25HNBCarrier single-stage communicating HP

What the control is telling you

Amber STATUS light flashes 32. Suction pressure dropped below the trip point (cooling about 33 psig or less, heating about 15 psig or less). After 3 trips it becomes code 83 (4-hour lockout). Type: Local; reset: 6 minutes.

Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8 (AOC control + inverter)

Likely causes

  • See code 83 for causes

Test and repair steps

  1. Troubleshoot as code 83 (charge, airflow, closed valve, restriction, EXV/TXV).

Models that show this code

15 models in Carrier Infinity 18VS 25VNA8, Carrier 2-stage 24ANB/25HNB, Carrier single-stage communicating HP

25HNB62425HNB63625HNB64825HNB66025HNB92425HNB93625HNB94825HNB96025VNA81325VNA82425VNA82525VNA83625VNA83725VNA84825VNA860

Other codes on the same units

  • 16 Lost communication with user interface
  • 25 Invalid model plug / inverter size
  • 31 High pressure switch open
  • 33 Lost inverter communication
  • 45 Outdoor control board failure
  • 46 Brownout
  • 47 No 230 V at unit
  • 48 Lost inverter communication - lockout

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.19. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.