Bosch · Air handler
2 flashes Indoor T2 sensor fault
What the control is telling you
The coil temperature sensor reads faulty.
Applies to: Bosch IDS Plus/Premium BIVA20 R-454B air handlers (2-5 ton)
Likely causes
- Sensor not seated
- Failed sensor
Test and repair steps
- Reseat the T2 sensor.
- Replace it if the resistance is 0 or very high.
- Replace the board if it persists.
Models that show this code
4 models in Bosch IDS Plus/Premium air handler
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Bosch IDS Plus/Premium air handler BIVA20 installation BTC 762003302 C (10.2024), section 13 LED Flashing Troubleshooting, p.49-50. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.